H12-421-ENU練習問題集で検証済みで更新された240問題あります [Q26-Q50]

Share

H12-421-ENU練習問題集で検証済みで更新された240問題あります

更新されたH12-421-ENU試験問題集でPDF問題とテストエンジン

質問 26
ECC800 default management authority user name is admin, admin has all the rights to operate the web interface function.

  • A. TRUE
  • B. FALSE

正解: A

 

質問 27
UPS2000-G-(6-20kVA) battery discharge time is significantly lower than the standard time may be caused by what? (Multiple choice)

  • A. No mains input
  • B. The battery is not full
  • C. Battery capacity reduction
  • D. Increased load

正解: B,C,D

 

質問 28
The NetCol 8000-A compressor has a large amount of foam in the oil sight glass for a long time, indicating that the superheat is too large.

  • A. True
  • B. False

正解: B

 

質問 29
Which of the following are the characteristics of Huawei NetCol5000-A row-level precision air conditioner cooling capacity adjustment?

  • A. When the load is lower than 20%, the electric heating heat compensation is turned on, and the compressor is continuously operated without stopping.
  • B. Invariable frequency compressor, can't adjust cooling capacity infinitely.
  • C. When the load is lower than 30%, the compressor starts and stops frequently, and the valve frequently actions and is easily stuck.
  • D. DC inverter compressor, which can 20%~100% infinitely adjust cooling capacity.

正解: A,D

 

質問 30
When the NetCol5000-C commissions the drainage device, lift the high floater by hand for 5 seconds. At this time, the dual water pump is turned on at the same time, and the "discharge abnormality alarm" appears.

  • A. TRUE
  • B. FALSE

正解: A

 

質問 31
ECC800 does not support historical data export.

  • A. True
  • B. False

正解: B

 

質問 32
Which of the following factors affect battery life? (Multiple Choice)

  • A. Number of cycles
  • B. Temperature
  • C. Depth of discharge
  • D. Rated capacity

正解: A,B,C

 

質問 33
The data center energy efficiency PUE is as small as possible, and the minimum can be close to zero.

  • A. True
  • B. False

正解: B

 

質問 34
In general, the air supply distance of the air duct is shorter than that of the hood air supply.

  • A. TRUE
  • B. FALSE

正解: B

 

質問 35
After the air conditioner is commissioned, the indoor temperature is in a reasonable state, and the suction pressure is not lower than ( ).

  • A. 7MPa
  • B. 6Mpa
  • C. 5MPa
  • D. 0.7MPa

正解: D

 

質問 36
DOD (depth of discharge) indicates the percentage of battery discharge and battery rated capacity.

  • A. True
  • B. False

正解: A

 

質問 37
When the UPS2000-G-(6-20kVA) is in ECO mode, the battery indicator and bypass indicator are on at the same time.

  • A. True
  • B. False

正解: B

 

質問 38
When installing the UPS battery, the installation tool does not need to be insulated because the load is not charged.

  • A. True
  • B. False

正解: B

 

質問 39
In the naming of UPS5000-E-120K-HASBS, the letter E stands for ().

  • A. Input switch type is MCCB
  • B. Input switch type is ATS
  • C. E series modular UPS
  • D. 208V voltage system

正解: C

 

質問 40
The NetCol5000-A35kW air conditioner has a light load dehumidification function.

  • A. True
  • B. False

正解: B

 

質問 41
The reasonable exhaust pressure range of NetCol5000-A is ( ) Mpa. (Multiple choice)

  • A. 2.5~3.8 ( 35~45° )
  • B. 1.5~2.5 ( below 15° )
  • C. 3.1~4.15 ( above 45° )
  • D. 1.5 ~3.1 ( 15~35° )

正解: A,B,C,D

 

質問 42
The device accesses the ECC800 monitoring system through a smart ETH socket, using the () interface of the intelligent FTH socket.

  • A. PoE
  • B. AI/DI
  • C. FE
  • D. RS485

正解: A

 

質問 43
Which humidifier is used by the NetCol 8000-A?

  • A. Infrared humidifier
  • B. Electrode humidifier
  • C. High pressure micro-mist humidifier
  • D. Wet film humidifier

正解: A

 

質問 44
How many kVA power modules does the UPS5000-S-400K use?

  • A. 0
  • B. 1
  • C. 2
  • D. 3

正解: B

 

質問 45
When the NetCol5000-A removes the air conditioning humidifier, the steps to maintain the electrode humidifier include (). (Multiple choice)

  • A. Replace the hardened and brittle hose thoroughly flush the drain
  • B. Disconnect the water supply valve and drain valve wiring
  • C. Remove and clean the water supply valve
  • D. Remove the drain tank and drain valve component

正解: A,B,C,D

 

質問 46
What are the access control type of the micro module? (Multiple Choice)

  • A. Fingerprint swipe access control machine
  • B. Fingerprint password swipe access control machine
  • C. Face recognition access control
  • D. Password swipe access control machine

正解: A,B,D

 

質問 47
When the single machine is working, after the function of power-off of the ups2000-g machine is prohibited, the PL port has no output when overload or battery power is low.

  • A. True
  • B. False

正解: B

 

質問 48
At present, the industry PUE value can be optimally achieved ( ).

  • A. 1.06
  • B. 0
  • C. 0.5
  • D. -0.5

正解: A

 

質問 49
When the device interface uses the Modbus-RTU protocol, what needs to be installed when accessing the ECC800?

  • A. AC actuator
  • B. ETH converter
  • C. Access control actuator
  • D. sunroof actuator

正解: B

 

質問 50
......